SU4000 AC Drives (V/F & Sensorless Vector Control)
UNIVERSAL FREQUENCY INVERTER

This series AC Drives are sensorless vector control AC Drives and could be converted between Vector control and V/F control. Our AC Drives are programmed by PC tools by using MODBUS PROTOCOL through RS485. AC Drives >3.7KW are in metal cover.
1、INDIVIDUAL DATA SHEET
Type |
Input
Voltage |
MOTOR
G type / P type
(KW) |
Output
Current
(A) |
Power
(KW) |
Drive Capacity(KVA) |
Size:(mm) |
| SU405D5G07D7P43A | Three phases 400V 50Hz | 5.5/7.5 |
14/18 |
5.5/7.5 |
11/14 |
123*350*191 |
| SU407D5G0011P43A | Three phases 400V 50Hz | 7.5/11 |
18/27 |
7.5/11 |
14/21 |
123*350*191 |
| SU40011G0015P43A | Three phases 400V 50Hz | 11/15 |
27/34 |
11/15 |
21/26 |
153*453*217 |
| SU40015G0018P43A | Three phases 400V 50Hz | 15/18.5 |
34/41 |
15/18.5 |
26/34 |
153*453*217 |
| SU418D5G0022P43A | Three phases 400V 50Hz | 18.5/22 |
41/52 |
18.5/22 |
31/40 |
180*480*278 |
| SU40022G0030P43A | Three phases 400V 50Hz | 22/30 |
52/65 |
22/30 |
40/50 |
180*480*278 |
| SU40030G0037P43A | Three phases 400V 50Hz | 30/37 |
65/80 |
30/37 |
50/61 |
180*560*278 |
| SU40037G0045P43A | Three phases 400V 50Hz | 37/45 |
80/96 |
37/45 |
61/73 |
180*560*278 |
| SU40045G0055P43A | Three phases 400V 50Hz | 45/55 |
96/128 |
45/55 |
73/98 |
273*750*326 |
| SU40055G0075P43A | Three phases 400V 50Hz | 55/75 |
128/165 |
55/75 |
98/130 |
273*750*326 |
| SU40075G0090P43A | Three phases 400V 50Hz | 75/90 |
165/185 |
75/90 |
130/153 |
415*766*340 |
| SU40090G0110P43A | Three phases 400V 50Hz | 90/110 |
185/224 |
90/110 |
153/170 |
415*766*340 |
| SU40110G0132P43A | Three phases 400V 50Hz | 110/132 |
224/260 |
110/132 |
170/211 |
479*976*402 |
| SU40132G0160P43A | Three phases 400V 50Hz | 132/160 |
260/302 |
132/160 |
211/230 |
479*976*402
|
| SU40160G0185P43A | Three phases 400V 50Hz | 160/185 |
302/340 |
160/185 |
230/260 |
545*986*457 |
| SU40185G0220P43A | Three phases 400V 50Hz | 185/220 |
340/450 |
185/220 |
260/340 |
545*986*457
|
| SU40220G0250P43A | Three phases 400V 50Hz | 220/250 |
450/470 |
220/250 |
340/360 |
643*1231*494
|
| SU40250G0280P43A | Three phases 400V 50Hz | 250/280 |
470/520 |
250/280 |
360/390 |
643*1231*494
|
| SU40280G0315P43A | Three phases 400V 50Hz | 280/315 |
520/605 |
280/315 |
390/460 |
643*1231*494
|
| SU40315G0350P43A | Three phases 400V 50Hz | 315/350 |
605/640 |
315/350 |
460/520 |
643*1231*494 |
2、TECHNICAL DATA
SERIES |
SU4000 |
|
Input |
Rated voltage frequency range |
400V/50Hz/60Hz, voltage:+/-15%;frequency:+/-5% 200V/50Hz/60Hz, voltage:+/-15%;frequency:+/-5% |
Output |
Rated voltage |
Three Phases: 200V
Three Phases: 400V |
Control
characteristic |
Control way |
PWM Voltage Vector Control |
Control mode |
V/F Control / Sensorless Vector Control |
|
frequency range |
0.1 ~400Hz |
|
Frequency precision |
digital:±0.01%( -10℃~ +40℃ ) |
|
analogue:highest frequencyX 0.2%Hz ( 25℃ +/-10% ) |
||
Frequency setting |
digital:0.01 Hz |
|
analogue:highest frequency X 0.1%Hz |
||
Output detinition |
0.01 Hz |
|
Over load capacity |
general type:150% of rated output current per minute
exhaust fan,water pump:120% of rated output current per miniute |
|
Frequency setting signal |
0~+10V(20kΩ), 4~20mA(250Ω) |
|
Speed up and down |
0.0~3600second (setting speed up and down seperately) |
|
Brake rotation moment |
125%with braking resitance,20%without |
|
V/f mode |
15 presetting VF and programing VF |
|
Protection
function |
Overload protection |
electronic overheat relay protection |
Instantaneous over current flow |
general typeG:250% of inverter rated current flow
exhaust fan,water pumpP: 200% of inverter rated current flow |
|
Over load |
general typeG:motor stops after 1 minute of 150%rated current flow exhaust fan,water pumpP:motor stops after 1minute of 120% rated current flow . |
|
Over voltage |
rectifier output 380V(200V grade)/760V(400V grade)
or lower,motor stops. |
|
Low voltage |
rectifier reduce output to 190V(200V grade)/380V(400V grade)or lower, motor stops. |
|
Instantaneous power off |
instantaneous power off over 15 ms or over, stop running it keep running when instantaneous power off less than 2 second. |
|
Radiator overheat |
thermal resistance protection. |
|
Speedless protection |
speedless protection during constant speed or speed up and down. |
|
Grounding problem |
protected by electronic circuit. |
|
environment |
Temperature humidity |
-10℃~+40℃,90% relatively. |
place |
Indoor (avoid dust and corrosive gas). |
|
elevation |
below 1000 meters. |
|
vibration |
below 0.5G |
|
3、DIMENSION
|
|
![]() |
|
![]()